 larger image
| Applications Directly buried or installed in ducts for 600 volt secondary distribution.
Construction Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.
Standards Secondary UD single conductor 600V cable meets or exceeds the following ASTM specifications.
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
Secondary UD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
"USE-2" per UL 854 available upon request.
Options
Cable in Duct (CIC)
Abrasion Resistant
Ampacity 90oC conductor temperature, 20oC ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
|  |
| | | Code Name |  | Emory
|  | Size AWG or MCM |  | 500
|  | Stranding |  | 37/W
|  | Insulation Thickness |  | 95 mls
|  | Outside Diameter |  | .979 Inches
|  | Weight Per 1000ft |  | 579 Lbs
|  | Ampacity Direct Burial |  | 465 Amps
|  | Ampacity In Duct |  | 370 Amps
|  |
| | | |
|
|